Excluding the regions of Crimea, Donetsk and Luhansk
Petro-Canada™ Lubricants' distribution network extends to over 80 countries worldwide
Petro-Canada Lubricants LUMINOL™ family of electrical insulating oils represents a breakthrough in electrical insulating oil technology. Unlike competitive products formulated with naphthenic mineral oils, LUMINOL™ uses ultra-pure, high quality base oils to deliver worry-free, corrosive sulfur-free performance in your transformer.
LUMINOL™ TRi is ideal for use in large power and distribution transformers as well as free-breathing units. LUMINOL™ LS is an electrical insulating oil for high voltage equipment in specialty applications. LUMINOL™ Di is ideal for use in smaller distribution transformers such as pad and pole mounted units. LUMINOL™ LV is an electrical insulating oil designed specifically for Siemens. X-ray equipment. LUMINOL™ electrical insulating oils are suitable for commercial, industrial and institutional applications:
LUMINOL™ TRi meets or exceeds the performance requirements of CAN / CSA-C50-14 (R2018) (Class A and B), ASTM D3487 standards, and DOBLE TOPS specifications.
LUMINOL™ TRi meets the CSA-C50-14 (R2018) upgraded oxidation stability Special Requirements for Type IV fluids oil.
LUMINOL™ TRi is designed for Type II and Type IV applications and meets IEC 60296 General specifications for fully inhibited high grade oil (Type A).
LUMINOL™ TRi is approved for applications requiring Ontario Hydro M-104.
LUMINOL™ LS is designed for Type II applications and meets or exceeds the performance requirements of CAN / CSA-C50-14 (R2018) (Class A and B), ASTM D3487 standards.
LUMINOL™ Di meets the performance requirements of CAN / CSA-C50-14 (R2018) Class B and ASTM D3487. It is designed for Type II applications.
Typical characteristics are shown below:
|
LUMINOL™ TRI |
LUMINOL™ LS |
LUMINOL™ DI |
---|---|---|---|
Viscosity, cSt @ 40°C |
9.2 |
9.1 |
9.35 |
Viscosity, cSt @ 0°C |
53 |
48.4 |
55.5 |
Viscosity, cSt @ -40°C |
1,230 |
1,223 |
4,082 |
Flash Point, COC, °C/°F |
170/338 |
171/340 |
171/340 |
Pour Point, °C/°F |
-60/-76 |
-60/-76 |
-48/-54 |
Dielectric breakdown voltage, after treatment - 60Hz, 2mm gap (ASTM D1816), kV |
65 |
62 |
68 |
Power Factor @ 60Hz, 100°C |
0.001 |
0.001 |
0.001 |
Interfacial Tension, 25°C, mN/m |
48 |
48 |
46 |
Rotary Pressure Vessel Oxidation Test (ASTM D2112), minutes |
600 |
592 |
451 |
Gassing Tendency (ASTM D2300), µL/min |
-10 |
+11.7 |
+23.6 |
Oxid. Stability, wt% Sludge (IEC 61125 C, 500 h) |
<0.02 |
– |
– |
Oxid. Stability, Neut # mg KOH/g (IEC 61125 C, 500 h) |
<0.02 |
– |
– |
Oxid. Stability, Power Factor @ 90°C (IEC 61125 C, 500 h) |
<0.001 |
– |
– |