Excluding the regions of Crimea, Donetsk and Luhansk
Petro-Canada™ Lubricants' distribution network extends to over 80 countries worldwide
Petro-Canada Lubricants LUMINOL™ family of electrical insulating oils represents a breakthrough in electrical insulating oil technology. Unlike competitive products formulated with naphthenic mineral oils, LUMINOL™ uses ultra-pure, high quality base oils to deliver worry-free, corrosive sulfur-free performance in your transformer.
LUMINOL™ TRi is ideal for use in large power and distribution transformers as well as free-breathing units. LUMINOL™ LS is an electrical insulating oil for high voltage equipment in specialty applications. LUMINOL™ Di is ideal for use in smaller distribution transformers such as pad and pole mounted units. LUMINOL™ LV is an electrical insulating oil designed specifically for Siemens. X-ray equipment. LUMINOL™ electrical insulating oils are suitable for commercial, industrial and institutional applications:
LUMINOL™ TRi meets or exceeds the performance requirements of CAN / CSA-C50-14 (R2018) (Class A and B), ASTM D3487 standards, and DOBLE TOPS specifications.
LUMINOL™ TRi meets the CSA-C50-14 (R2018) upgraded oxidation stability Special Requirements for Type IV fluids oil.
LUMINOL™ TRi is designed for Type II and Type IV applications and meets IEC 60296 General specifications for fully inhibited high grade oil (Type A).
LUMINOL™ TRi is approved for applications requiring Ontario Hydro M-104.
LUMINOL™ LS is designed for Type II applications and meets or exceeds the performance requirements of CAN / CSA-C50-14 (R2018) (Class A and B), ASTM D3487 standards.
LUMINOL™ Di meets the performance requirements of CAN / CSA-C50-14 (R2018) Class B and ASTM D3487. It is designed for Type II applications.
Typical characteristics are shown below:
| 
 | LUMINOL™ TRI | LUMINOL™ LS | LUMINOL™ DI | 
|---|---|---|---|
| Viscosity, cSt @ 40°C | 9.2 | 9.1 | 9.35 | 
| Viscosity, cSt @ 0°C | 53 | 48.4 | 55.5 | 
| Viscosity, cSt @ -40°C | 1,230 | 1,223 | 4,082 | 
| Flash Point, COC, °C/°F | 170/338 | 171/340 | 171/340 | 
| Pour Point, °C/°F | -60/-76 | -60/-76 | -48/-54 | 
| Dielectric breakdown voltage, after treatment - 60Hz, 2mm gap (ASTM D1816), kV | 
 65 | 
 62 | 
 68 | 
| Power Factor @ 60Hz, 100°C | 0.001 | 0.001 | 0.001 | 
| Interfacial Tension, 25°C, mN/m | 48 | 48 | 46 | 
| Rotary Pressure Vessel Oxidation Test (ASTM D2112), minutes | 
 600 | 
 592 | 
 451 | 
| Gassing Tendency (ASTM D2300), µL/min | -10 | +11.7 | +23.6 | 
| Oxid. Stability, wt% Sludge (IEC 61125 C, 500 h) | 
 <0.02 | 
 – | 
 – | 
| Oxid. Stability, Neut # mg KOH/g (IEC 61125 C, 500 h) | 
 <0.02 | 
 – | 
 – | 
| Oxid. Stability, Power Factor @ 90°C (IEC 61125 C, 500 h) | 
 <0.001 | 
 – | 
 – |